Technical Reference
Use this chart to
determine
parameter ranges, limits and default settings. Then enter your setting for
each
parameter.
Make a photocopy of the
chart
and enter values for each program you use.
Program
#
System
Programmer
Date
Series 1500 DIP Switch Settings
.
Sw-Position
Function
Setting
#1
-ON
Event Output
#4
for both
Ch-1
and Ch-2 are alarm outputs.
#1
-
OFF
1
Event Output
#4
for both
Ch-1
and Ch-2 are event outputs.
I
##2
-
ON
1
Alarms are latching (displayed until cleared manually).
I
#2
-
OFF
1
Alarms are non-latching (displayed only as tong as alarm condition exists).
I
#3-ON
I
The Ch-2 sensor is an
RTD
sensor. On the
(A007-1316)
board,
Jumper J149 must be on
Wl51,
Jumper
J152
must be on
W153.
I
#3-OFF
The Ch-2 input is a
0-5V
signal for 0-l 00% RH.
On the
(A007-1316)
board,
Jumper J149 must be on
W150,
Jumper J152 must be on Wl54.
#4-ON
Dual
PID
#4
-
OFF
1
Single
PID
#5
-
ON
1
Factory use only.
Must be in the ON position.
#6
-
ON
1
Cold Start on power-up.
(Memory
cleared, parameters set to default values)
I
I
1
#6
-
OFF
1
Warm Start on power-up. (Programmed values are retained for all parameters):
1
I
#7-ON
°C
function after a Cold Start.
#7
-
OFF
°F
function after a Cold Start.
#&OFF
Not Used. Set in the OFF position
OFF
RTD Series 1500 Parameter Ranges
Prompt
Parameter
Number of Steps
Step
Type
(Data
Comm.)
S1
Ch-1 Set Point
S2
Ch-2 Set Point
Fl
.
ON
(DIP
1
ON)
Dec.
Equiv
ON (DIP
1=ON)
Dec. Equiv.
E2
El
ON (DIP
1=OFF)
Dec. Equiv.
E2
ON (DIP
l=OFF)
Dec.
Equiv.
HR
Step Duration-Hours
MN
Step Duration-Minutes
SC
Step Duration-Seconds
JC
Jump Step
1
or Ch-1 Actual
w2
Wait for Ch-2 Actual
WE
Wait for Event
WH
Wait for Real Hour
WM
Wait for Real Minute
WS
Wait for Real Second
Chart 4
-
General Parameter
Chart,
Chapter 4
Range
Low
High
Units
1
51
Steps
0
3
Type
Ll U1
°F/°C
L2
u2
%RH/°F/°C
0
15
N
0
15
binarv total ON
0
7
binarv total ON
0
7
binarv total ON
0
24
hours
0
59
minutes
0
59
seconds
1
51
Step#
JC Jump Counts 0
255
counts
11
U1
L2
U2
%RH/°F/°C
0
1
-
0 23
hours
0
59
minutes
0
59
,
seconds
WATLOW Series
1500
User's
Manual
55